Vapour compression system analysis
Turn field readings into a clear diagnostic direction.
Enter whatever reliable measurements are available. CycleCheck derives compatible missing values, compares the cycle against the selected application, and ranks faults worth investigating.
Call setup
Expected ranges and approach calculations change with the application and equipment.
A repeatable diagnostic process
Use patterns across the air side and refrigerant side instead of making a decision from one number.
1. Stabilize before judging charge
Confirm clean heat exchangers, correct fan rotation and speed, open dampers and valves, and a representative load. Allow pressures and temperatures to settle. Pull-down and near-setpoint operation are valid conditions, but their expected ranges are different.
2. Match pressure and pipe temperatures
Superheat and subcooling are only meaningful when pressure and line temperature represent the same circuit location and operating moment. Select the correct refrigerant and use dew/bubble values correctly for blends.
3. Use wet-bulb where moisture matters
Return and supply wet-bulb readings show total cooling response, including latent load. Outdoor wet-bulb is the correct ambient reference for an evaporative condenser; air-cooled equipment normally uses entering dry-bulb.
4. Separate look-alike faults
High superheat can result from low charge, a restriction, low airflow, or high load. Subcooling, coil temperature differences, current, and non-invasive temperature drops help separate those causes before the sealed system is disturbed.
Field readings
Blank fields are allowed. Blue values are inferred from compatible measurements.
Air-side measurement notes
Take return and supply readings at representative points, not directly in the coil's coldest discharge stream. A high dry-bulb split alone does not prove good airflow: restricted airflow can increase split while reducing capacity. Wet-bulb readings help identify when a small dry-bulb split is explained by heavy latent load.
Low-side measurement notes
Evaporator superheat describes the coil outlet; total superheat at the compressor helps assess floodback risk and suction-line heat gain. Excessive line gain can point to missing insulation, a hot routing, or a long line set and should not be mistaken for evaporator superheat.
Condenser approach and heat-rejection notes
Air-cooled: SCT minus entering dry-bulb is commonly called condensing split or CTOA. Evaporative: SCT minus entering wet-bulb is the useful approach. Water-cooled: SCT minus leaving condenser-water temperature is the refrigerant-to-water approach. Keep the condenser type correct so the app uses the right reference.
Supporting non-invasive check notes
Use matched, insulated pipe probes and allow them to settle. A filter-drier temperature drop is supporting evidence, not proof by itself; confirm pressure drop or flash gas where practical. Compare compressor current with expected load, voltage, and manufacturer performance data rather than treating RLA as a target amperage.