Refrigerant Line Sizer

ASHRAE-method pipe sizing & copper material takeoff

System

Lowest unloading step / smallest active evap

Line runs

Suction evaporator → compressor

evap below compressor

Liquid condenser / receiver → evaporator

condenser below evap (lift)

Multiple evaporators

Materials

clevis + saddle cushion clamp split-ring

System schematic

Line details

Enter system data to size lines.

Material list

Method & sources

Sizing follows the equivalent-length / saturation-temperature-penalty method of McQuay AG 31-011 “Refrigerant Piping Design Guide” (ASHRAE Refrigeration Handbook Ch. 2) for R-410A, R-22, R-134a and R-407C (capacities in tons, corrected for SST, condensing temperature, equivalent length and design ΔT with the 0.55-exponent relation), and the Hussmann “Line Sizing Refrigeration Data Guide” (MBH tables) for R-404A/R-507A and R-448A/R-449A. R-454B, R-454A, R-454C, R-1234yf and R-513A use the manufacturer capacity tables from the Chemours “Opteon Refrigerant Piping Handbook” (pp. 22–28, Type L copper, −60 to +40 °F SST), with condensing-temperature multipliers and riser oil-return minimums borrowed (capacity-scaled) from the closest AG 31-011 refrigerant. R-32 uses the R-410A tables per Daikin AG-TP-111 practice; R-290 and R-600a are derived from the R-22 / R-134a tables by published volumetric-capacity ratios (Danfoss hydrocarbon application data) — verify flammable-refrigerant designs with the equipment manufacturer. R-717 (ammonia) is intentionally not sized: ammonia prohibits copper and uses steel piping per ASHRAE/IIAR practice. Suction and discharge risers are checked against minimum-capacity oil-return tables; liquid lines are checked for velocity and for subcooling to offset friction plus static lift. Vertical risers automatically include a P-trap at the base and an inverted trap at the top — each counted as two 90° elbows in both equivalent length and the material list (DuPont handbook / Carrier practice; per AG 31-011, intermediate traps are unnecessary in a properly sized riser). Fitting equivalent lengths from ASHRAE (AG 31-011 Tables 4–5). Copper temper and lengths per the CDA Copper Tube Handbook; insulation per the Armacell AP Armaflex submittal. Full citations: SOURCES.md in this folder.

Assumptions: Type L / ACR copper sized by OD · design ΔT 2°F suction, 1°F discharge and liquid (A/C) · tables at 15°F superheat · verify final design against equipment manufacturer requirements. This tool is a design aid, not a substitute for engineering judgment.